FlexWash has a network integration for Elka and Magnetic MGC-PRO gates with their ethernet modules. All other gates use the relay integration described on this page. For stoplights, see Relay Stoplights.
Requirements
The FlexWash-provided ioLogik does two things:- Sends an open command. When a vehicle is cleared to proceed, FlexWash closes a relay contact for 1.5 seconds.
- Reads the closed state. FlexWash reads a dry contact on a digital input. The contact must be closed while the gate is closed and open while the gate is open. This input is required.
- An open input that opens the gate when the relay closes.
- Automatic closing, triggered by a safety loop, a timer, or both.
- A closed status output: a dry contact that is closed while the arm is down.

Responsibilities
FlexWash supports the ioLogik interface described on this page. We do not design, install, troubleshoot, or support the gate or its controller.
How the Interface Works

- At rest, the gate is closed. The closed contact is closed, so the digital input reads ON.
- When a vehicle reaches the front of the gate queue, FlexWash closes the relay for 1.5 seconds. The gate controller treats this like a pressed open button.
- The gate opens. The closed contact opens and the digital input reads OFF. FlexWash shows the gate as open.
- The vehicle drives through. The gate controller closes the gate when the safety loop clears or the close timer expires.
- The closed contact closes again. FlexWash marks the gate closed and, after a 2 second settling period, releases the next vehicle.
FlexWash ignores the closed contact for 2 seconds after it sends the open command. The closed contact must open within those 2 seconds. If it still reads closed, FlexWash treats the gate as closed and releases the next vehicle.
The ioLogik E1214

FlexWash configures the relay channels for pulse output and manages the network settings. Do not change the ioLogik configuration.
Relay Output Wiring
Wire the gate controller’s open input to the NO and C terminals of the assigned relay. The first gate usesR0_NO and R0_C.
The relay is a dry contact. It carries whatever the gate controller puts on it, up to 5 A resistive at 250 VAC or 30 VDC. Most open inputs are low-voltage dry contact inputs. Keep line voltage off the ioLogik terminals.
Before you connect the wires to the ioLogik, short them together by hand. The gate should open, then close on its own. If it does not, fix the gate controller settings first.
Digital Input Wiring
Wire the closed status contact betweenDI0 and GND. Leave COM unconnected.

DI0to one side of the closed status contactGNDto the other side of the closed status contactCOMnot used
- Contact closed: DI0 is shorted to GND. The ioLogik reads ON. FlexWash shows the gate closed.
- Contact open: the ioLogik reads OFF. FlexWash shows the gate open.
Dry contact wiring is electrically isolated and needs no external power supply. FlexWash supports dry contacts only. Never put voltage on a digital input.
Induction Loops
The gate’s own loops, such as the safety and closing loops, stay wired to the gate controller. FlexWash does not need them. Wire a loop to the ioLogik only when FlexWash must read it, for example a merge loop that confirms the previous vehicle has moved into the tunnel. Wire the loop detector’s spare presence contact between a spare digital input andGND the
same way. The ioLogik reads ON as occupied.
Multiple Channels
FlexWash supports one E1214 per site, for up to six relay gates or stoplights. It has six relays (R0 to R5) and six digital inputs (DI0 to DI5). Each
gate uses one relay and one digital input. Wire additional gates to R1 and
DI1, R2 and DI2, and so on. Tell FlexWash support which channels you wired
so our configuration matches.
All six digital inputs share one GND terminal. When you add a wire to it, tug
test every wire already in the terminal. Seating a new wire can loosen the others.
Vendor Specific Instructions
Giotto
Programming
The keypad has three buttons. From top to bottom: +, -, and OK. To exit the current menu, press + and - at the same time, then release.
- Press OK once. The screen shows
LANG, then the current language. - If the language is not
EnG, use + or - to selectEnGand press OK. - Exit the menu until you are back at the main screen. Do not press OK again after you select the language.
- Press OK twice quickly. The screen shows
hALTorALT. Press OK. - The screen scrolls a message such as
FoLLoW thE USEr GUIdE. Press OK to skip it. - The screen shows
PArAM. Use + or - to go toLoGIcand press OK. - Set each parameter below. For each one, use + or - to go to the parameter, press OK, set the value, and press OK again. The screen flashes
PRGto confirm and returns to the logic menu.
- Exit the menus until you are back at the main screen.

Wiring
With the programming above, wire the Giotto terminals to the ioLogik as follows. The first gate uses relayR0 and digital input DI0.
Before you connect terminals 26 and 27, check them with a multimeter as described in Digital Input Wiring.